FLAT&EARTH
Technical Data :
Max. Operating Temperature : 70°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 12xD
Test Voltage : 2 kV
Voltage Rating : 300/500 V
Construction :
Sheath : PVC (Polyvinyl Chloride)
Armour : –
Filler : –
Insulation : PVC (Polyvinyl Chloride)
Conductor : Solid or Stranden Copper Conductor (Class 1-Class2)
Code :
6242 Y / 6243 Y , CU/PVC/PVC
Standards :
BS 6004
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant
Application :
Used as surface wiring where there is little mechanical damage risk or in conduit.
Nominal Cross Section |
Overal Diameter |
Net Weight |
Delivery Length |
Resistance at 20°C |
Current Carrying Capacity |
|
(mm²) | (mm) | (kg/km) | (m) | (ohm/km) | In Ground at 20°C | In Air at 30°C |
2x1+1 | 7,6 x 4,1 | 70 | 100 | 18,1 - 18,1 | - | 13 |
2x1,5+1 | 8,4 x 4,6 | 91 | 100 | 12,1 - 18,1 | - | 16 |
2x2,5+1,5 | 10,0 x 5,3 | 128 | 100 | 7,41 - 12,1 | - | 21 |
2x4+1,5 | 11,5 x 6,1 | 184 | 100 | 4,61 - 12,1 | - | 27 |
2x6+2,5 | 13,5 x 7,0 | 238 | 100 | 3,08 - 7,41 | - | 34 |
2x6+4 | 14,0 x 6,9 | 248 | 100 | 3,08 - 4,61 | - | 34 |
2x10+4 | 16,8 x 8,4 | 378 | 100 | 1,83 - 4,61 | - | 45 |
2x10+6 | 17,2 x 8,4 | 397 | 100 | 1,83 - 3,08 | - | 45 |
2x16+6 | 19,7 x 9,6 | 543 | 100 | 1,15 - 3,08 | - | 57 |
3x1+1 | 9,9 x 4,1 | 94 | 100 | 18,1 - 18,1 | - | 13 |
3x1,5+1 | 11,2 x 4,6 | 121 | 100 | 12,1 - 18,1 | - | 16 |
3x2,5+1 | 13,1 x 5,3 | 173 | 100 | 7,41 - 18,1 | - | 21 |
3x4+1,5 | 15,8 x 6,3 | 252 | 100 | 4,61 - 12,1 | - | 27 |
3x6+2,5 | 17,9 x 6,9 | 342 | 100 | 3,08 - 7,41 | - | 34 |
3x10+4 | 22,8 x 8,4 | 540 | 100 | 1,83 - 4,61 | - | 45 |
3x16+6 | 26,8 x 9,6 | 789 | 100 | 1,15 - 3,08 | - | 57 |