Technical Data :

Max. Operating Temperature : 70°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 6xD
Test Voltage : 2 kV, 2,5 kV
Voltage Rating : 300/500 V , 450/750 V

Construction :

Sheath : –
Armour : –
Filler : –
Insulation : PVC (Polyvinyl Chloride)
Conductor : Solid or Stranded Copper Conductor

Code :

H05V-K, H07V-K, CU/PVC

Standards :

EN 50525-2-31 , VDE 0281 , IEC 60227 , BS 6004
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant

Application :

In dry rooms, switch and distribution boards, for laying in conduit on and under plaster and on insulating supports above plaster

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
1x0,50* 2.1 9 100 39.0 - -
1x0,75* 2.3 11 100 26.0 - 16
1x1* 2.5 14 100 19.5 11 20
1x1,5 2.9 20 100 13.3 14.5 24
1x2,5 3.6 31 100 7.98 19.5 32
1x4 4.1 45 100 4.95 26 42
1x6 4.7 75 100 3.30 34 54
1x10 5.9 106 100 1.91 46 73
1x16 6.9 165 100 1.21 61 98
1x25 8.7 260 1000 0.780 80 129
1x35 9.7 355 1000 0.554 99 158
1x50 11.6 502 1000 0.386 119 198
1x70 13.2 685 1000 0.272 151 245
1x95 15.3 921 1000 0.206 182 292
1x120 16.8 1132 1000 0.161 210 344
1x150 18.8 1425 1000 0.129 240 391
1x185 21.1 1832 1000 0.106 273 448
1x240 23.6 2290 1000 0.0801 320 528
1x300 26.2 2955 1000 0.0641 - 689
1x400 30.1 3995 1000 0.0486 - 789
1x500 34.2 5140 1000 0.0384 - -