H05Z1-K & H07Z1-K

  1. Flexible Copper Conductor (Class 5)
  2. HFFR Compound Insulation

Technical Data :

Max. Operating Temperature : 70 °C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 6xD
Test Voltage : 2 kV , 2,5 kV
Voltage Rating : 300/500 V , 450/750 V

Construction :

Sheath : –
Armour : –
Filler : –
Insulation : HFFR Compound
Conductor : Flexible Copper Conductor (Class 5)

Code :

H05Z1-K, H07Z1-K, CU/HFFR

Standards :

EN 50525-3-31 , VDE 0282 , BS 7211
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant
EN 61034 : Smoke Density
EN 50267 : Halogen Free

Application :

Used in energy networks in rafineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire.

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
1x0,50* 2.1 9 100 39.0 - 12
1x0,75* 2.3 11 100 26.0 - 15
1x1* 2.4 15 100 19.5 11 19
1x1,5 2.9 21 100 13.3 14 24
1x2,5 3.5 33 100 7.98 19 32
1x4 4.0 46 100 4.95 26 42
1x6 4.6 66 100 3.30 34 54
1x10 5.9 108 100 1.91 46 73
1x16 6.9 161 100 1.21 61 98
1x25 8.6 263 1000 0.780 80 129
1x35 9.7 362 1000 0.554 99 158
1x50 11.5 505 1000 0.386 119 198
1x70 13.2 689 1000 0.272 151 245
1x95 15.2 914 1000 0.206 182 292
1x120 16.7 1124 1000 0.161 210 344
1x150 18.7 1405 1000 0.129 240 391
1x185 21.0 1792 1000 0.106 273 448
1x240 23.5 2256 1000 0.0801 320 528
1x300 26.2 2811 1000 0.0641 - 564
1x400 30.0 3829 1000 0.0486 - -
1x500 34.1 4855 1000 0.0384 - -
1x630 37.9 6172 1000 0.0287 - -