H07V-R

  1. Stranded Copper Conductor (Class 2)
  2. PVC (Polyvinyl Chloride) Insulation

Technical Data :

Max. Operating Temperature : 70°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 12xD
Test Voltage : 2 kV, 2,5 kV
Voltage Rating : 300/500 V , 450/750 V

Construction :

Sheath : –
Armour : –
Filler : –
Insulation : PVC (Polyvinyl Chloride)
Conductor : Stranded Copper Conductor (Class 2)

Code :

H05V-R , H07V-R, CU/PVC

Standards :

EN 50525-2-31 , VDE 0281 , IEC 60227 , BS 6004
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant

Application :

In dry rooms, switch and distribution boards, for laying in conduit on and under plaster and on insulating supports above plaster

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
1x0,50* 2.1 9 100 36.0 - -
1x0,75* 2.2 12 100 24.5 - -
1x1* 2.4 15 100 18.1 - -
1x1,5 2.9 21 100 12.1 14.5 24
1x2,5 3.6 34 100 7.41 19.5 32
1x4 4.1 49 100 4.61 26 42
1x6 4.7 69 100 3.08 34 54
1x10 6.0 113 100 1.83 46 73
1x16 7.0 172 100 1.15 61 98
1x25 8.6 267 1000 0.727 80 129
1x35 9.8 358 1000 0.524 99 158
1x50 11.6 496 1000 0.387 119 198
1x70 13.2 680 1000 0.268 151 245
1x95 15.5 942 1000 0.193 182 292
1x120 17.1 1160 1000 0.153 210 344
1x150 19,1 1445 1000 0.124 240 391
1x185 21.2 1813 1000 0.0991 273 448
1x240 24.1 2346 1000 0.0754 320 528
1x300 26.9 2992 1000 0.0601 - -
1x400 30.6 3767 1000 0.0470 - -
1x500 34.2 4916 1000 0.0366 - -
1x630 38.0 6087 1000 0.0283 - -