H07V2-K

  1. Flexible Copper Conductor (Class 5)
  2. Heat Resistance PVC (Polyvinyl Chloride) Insulation

Technical Data :

Max. Operating Temperature : 90°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 6xD
Test Voltage : 2 kV, 2,5 kV
Voltage Rating : 450/750 V

Construction :

Sheath : –
Armour : –
Filler : –
Insulation : Heat Resistance PVC (Polyvinyl Chloride)
Conductor : Flexible Copper Conductor (Class 5)

Code :

H07V2-K, CU/PVC

Standards :

EN 50525-2-31 , VDE 0281 , IEC 60227 , BS 6004
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant

Application :

Heat resistance cables for internal wiring and switch , distribution boards

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
1x1,5 2.9 21 100 13.3 14.5 24
1x2,5 3.5 33 100 7.98 19.5 32
1x4 4.0 47 100 4.95 26 42
1x6 4.6 67 100 3.30 34 54
1x10 5.9 111 100 1.91 46 73
1x16 6.9 165 100 1.21 61 98
1x25 8.6 271 1000 0.780 80 129
1x35 9.7 374 1000 0.554 99 158
1x50 11.5 524 1000 0.386 119 198
1x70 13.1 714 1000 0.272 151 245
1x95 15.2 949 1000 0.206 182 292
1x120 16.7 1170 1000 0.161 210 344
1x150 18.7 1462 1000 0.129 240 391
1x185 21.0 1872 1000 0.106 273 448
1x240 23.5 2348 1000 0.0801 320 528
1x300 26.2 2952 1000 0.0641 - -
1x400 30.0 3995 1000 0.0486 - -