H07V2-R

  1. Stranded Copper Conductor (Class 2)
  2. Heat resistance PVC Insulation

Technical Data :

Max. Operating Temperature : 90°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 12xD
Test Voltage : 2 kV, 2,5 kV
Voltage Rating : 450/750 V

Construction :

Sheath : –
Armour : –
Filler : –
Insulation : Heat resistance PVC
Conductor : Stranded Copper Conductor (Class 2)

Code :

H07V2-R, CU/PVC

Standards :

EN 50525-2-31 , VDE 0281 , IEC 60227 , BS 6004
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant

Application :

When its required high operating temperatures (90°C) and for house hold appliances. It used as surface mounted or flush mounted in stationary plants. Dry places, distribution boards and closed spaces, factories workshops and kind of work places.

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
1x1,5 2.9 21 100 12.1 14.5 24
1x2,5 3.6 34 100 7.41 19.5 32
1x4 4.1 49 100 4.61 26 42
1x6 4.7 69 100 3.08 34 54
1x10 6.0 113 100 1.83 46 73
1x16 7.0 172 100 1.15 61 98
1x25 8.6 267 1000 0.727 80 129
1x35 9.8 358 1000 0.524 99 158
1x50 11.6 496 1000 0.387 119 198
1x70 13.2 680 1000 0.268 151 245
1x95 15.5 942 1000 0.193 182 292
1x120 17.1 1160 1000 0.153 210 344
1x150 19.1 1445 1000 0.124 240 391
1x185 21.2 1813 1000 0.0991 273 448
1x240 24.1 2346 1000 0.0754 320 528
1x300 26.9 2992 1000 0.0601 - -
1x400 30.6 3767 1000 0.0470 - -