H1Z2Z2-K
Technical Data :
Max. Operating Temperature : 120°C
Short Circuit Temperature : 200°C (max.5 sn)
Bending Radius : 6xD
Test Voltage : 6,5 kV
Voltage Rating : 1,0/1,0 kV
Construction :
Sheath : Cross Linked Halogen Free
Armour : –
Filler : –
Insulation : Cross Linked Halogen Free
Conductor : Tinned Flexible Copper Conductor (Class 5)
Code :
H1Z2Z2-K, CU-Sn / TPE / TPE, PV-1
Standards :
TS EN 50618
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant
EN 61034 : Smoke Density
EN 50267 : Halogen Free
Application :
It is suitable for use in fixed stationary indoor and outdoor installations, inside pipes , tubes and similar closed systems. It is designed to facilitate the connection of various photovoltaic system elements such a solar panels.
Nominal Cross Section |
Overal Diameter |
Net Weight |
Delivery Length |
Resistance at 20°C |
Current Carrying Capacity |
|
(mm²) | (mm) | (kg/km) | (m) | (ohm/km) | In Ground at 20°C | In Air at 30°C |
1x1,5 | 4.5 | 38 | 1000 | 13.7 | - | 30 |
1x2,5 | 4.9 | 49 | 1000 | 8.21 | - | 41 |
1x4 | 5,4 | 66 | 1000 | 5.09 | - | 55 |
1x6 | 6,0 | 87 | 1000 | 3.39 | - | 70 |
1x10 | 6,9 | 129 | 1000 | 1.95 | - | 98 |
1x16 | 8,1 | 188 | 1000 | 1.24 | - | 132 |
1x25 | 10,0 | 301 | 1000 | 0.795 | - | 176 |
1x35 | 11,3 | 417 | 1000 | 0.565 | - | 218 |
1x50 | 13,1 | 573 | 1000 | 0.393 | - | 276 |
1x70 | 14,9 | 782 | 1000 | 0.277 | - | 347 |
1x95 | 16,8 | 1011 | 1000 | 0.210 | - | 416 |
1x120 | 18,5 | 1251 | 1000 | 0.164 | - | 488 |
1x150 | 20,7 | 1564 | 1000 | 0.132 | - | - |
1x185 | 23,4 | 2002 | 1000 | 0.108 | - | - |
1x240 | 25,9 | 2500 | 1000 | 0.0817 | - | - |