NYIFY-R

  1. Stranded Copper Conductor (Class 2)
  2. PVC (Polyvinyl Chloride) Insulation
  3. PVC (Polyvinyl Chloride) Sheath

Technical Data :

Max. Operating Temperature : 70°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 12xD
Test Voltage : 2 kV
Voltage Rating : 300/500 V

Construction :

Sheath : PVC (Polyvinyl Chloride)
Armour : –
Filler : –
Insulation : PVC (Polyvinyl Chloride)
Conductor : Stranded Copper Conductor (Class 2)

Code :

NYIFY-R, CU/PVC/PVC

Standards :

VDE 0250 Teil 201
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant

Application :

Suitable for dry and humid areas. All type of factory , warehouse and depots where there is fire and explosion threat. Not suitable for underground. Used in fixed installations laying in conduit and under plaster.

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
2x1,5 13,3 x 4,1 81 1000 12.1 - 16
2x2,5 14,2 x 4,6 104 1000 7.41 - 21
2x4 16,0 x 5,5 147 1000 4.61 - 27
2x6 17,1 x 6,1 192 1000 3.08 - -
3x1,5 18,2 x 4,1 113 1000 12.1 - 16
3x2,5 20,4 x 4,5 152 1000 7.41 - 21
3x4 23,3 x 5,5 213 1000 4.61 - 27
3x6 25,4 x 6,3 290 1000 3.08 - -