NYIFY-U
Technical Data :
Max. Operating Temperature : 70°C
Short Circuit Temperature : 160 °C (max. 5sn.)
Bending Radius : 12xD
Test Voltage : 2 kV
Voltage Rating : 300/500 V
Construction :
Sheath : PVC (Polyvinyl Chloride)
Armour : –
Filler : –
Insulation : PVC (Polyvinyl Chloride)
Conductor : Solid Copper Conductor (Class 1)
Code :
NYIFY-U, CU/PVC/PVC
Standards :
VDE 0250 Teil 201
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant
Application :
Suitable for dry and humid areas. All type of factory, warehouse and depots where there is fire and explosion threat. Not suitable for underground. Used in fixed installations laying in conduit and under plaster.
Nominal Cross Section |
Overal Diameter |
Net Weight |
Delivery Length |
Resistance at 20°C |
Current Carrying Capacity |
|
(mm²) | (mm) | (kg/km) | (m) | (ohm/km) | In Ground at 20°C | In Air at 30°C |
2x1,5 | 12,9 x 4,0 | 78 | 1000 | 12.1 | - | 16 |
2x2,5 | 13,7 x 4,3 | 99 | 1000 | 7.41 | - | 21 |
2x4 | 15,4 x 5,2 | 142 | 1000 | 4.61 | - | 27 |
2x6 | 16,4 x 5,7 | 183 | 1000 | 3.08 | - | - |
3x1,5 | 17,7 x 4,0 | 109 | 1000 | 12.1 | - | 16 |
3x2,5 | 20,0 x 4,3 | 141 | 1000 | 7.41 | - | 21 |
3x4 | 22,4 x 5,2 | 206 | 1000 | 4.61 | - | 27 |
3x6 | 23,8 x 5,7 | 267 | 1000 | 3.08 | - | - |