RZ1-AK

  1. Flexible Aluminium Conductor (Class 5)
  2. XLPE (Cross-Linked Polyethylene) Insulation
  3. HFFR Filler
  4. HFFR Sheath (UV)

Technical Data :

Max. Operating Temperature : 90°C
Short Circuit Temperature : 250 °C (max. 5sn.)
Bending Radius : 6xD
Test Voltage : 3,5 kV
Voltage Rating : 0,6/1 kV

Construction :

Sheath : HFFR (UV)
Armour : –
Filler : HFFR
Insulation : XLPE (Cross-Linked Polyethylene)
Conductor : Flexible Aluminium Conductor (Class 5)

Code :

RZ1-AK AL / XLPE / HFFR

Standards :

TS IEC 60502-1
IEC 60228 : Conductor
IEC 60332-1 : Flame Retardant
EN 61034 : Low Smoke Density
EN 50267 : Halogen Free
EN 60332-3 : Vertical Flame Spread Test (Cat.C)

Application :

It is used in hotels, schools, hospitals, tunnels, refineries, high-rise buildings, data processing centers and business centers where people are concentrated, and in fire-sensitive areas.

Nominal Cross
Section
Overal
Diameter
Net
Weight
Delivery
Length
Resistance
at 20°C
Current
Carrying Capacity
(mm²) (mm) (kg/km) (m) (ohm/km) In Ground at 20°C In Air at 30°C
4x1,5 11,6 152 1000 21.1    
4x2,5 12,7 185 1000 12.63    
4x4 14,2 239 1000 7.21    
4x6 15,4 284 1000 5.15    
4x10 18,2 425 1000 3.08    
4x16 20,2 541 1000 1.91    
4x25 25,1 894 1000 1.20    
4x35 27,9 1105 1000 0.868    
4x50 31,3 1384 1000 0.641    
4x70 36,7 1844 1000 0.443    
4x95 41,6 2404 1000 0.320    
4x120 46,8 2950 500 0.253    
4x150 51,3 3541 500 0.206    
4x185 57,5 4381 500 0.164    
4x240 65,0 5637 250 0.125    
4x300 71,6 6805 250 0.100    
4x400 80,6 8675 250 0.0778    
4x500 90,2 11262 250 0.0605